Any Berkeley Lab employee, subcontractor, or affiliate who purchases or builds electrical utilization equipment for use at Berkeley Lab that has a potential of 50 volts or greater anywhere in the equipment
C. Exceptions
The following types of electrical equipment do not require inspection and approval prior to use:
- Unmodified NRTL-Listed Equipment: Equipment that is listed by an NRTL and has not been modified.
- Unused Equipment: Equipment that is not being used, e.g., in storage, staged for salvage or excess, etc. Equipment that is not being used must be labeled with the EQUIPMENT OUT OF SERVICE label (see Appendix B) so it is clear it is not in use.
- Equipment Granted Conditional Acceptance Under Work Process E: Prototype or proof-of-concept equipment (e.g., test chassis, benchtop experiment) in the process of being built to test the validity of a design and that is under the exclusive control of the designer if used for less than three months. Equipment being developed that exceeds a three-month period may be acceptable but requires Conditional Acceptance per Work Process E.
- Equipment Considered Nonhazardous: Equipment in any of the following categories is considered nonhazardous: Note: Equipment that is connected to AC only via a step-down transformer/AC adapter with voltage output less than 50 volts is exempt, but the transformer/AC adapter must be NRTL Listed.
Type
Range Considered Non-Hazardous
60 Hz AC
<50 V
>50 V and <5 mA
D. Policy Statement
The Berkeley Lab Electrical Equipment Safety Program (EESP) is designed to ensure the safe operation and installation of electrical utilization equipment.Anchor _Toc320885597 _Toc320885597 Anchor _Toc320885598 _Toc320885598 Anchor _Toc320885599 _Toc320885599 Anchor _Toc320885600 _Toc320885600 Anchor _Toc320885601 _Toc320885601 Anchor _Toc320885602 _Toc320885602 Anchor _Toc320885603 _Toc320885603 Anchor _Toc320885604 _Toc320885604 Anchor _Toc320885605 _Toc320885605 Anchor _Toc320885606 _Toc320885606 Anchor _Toc320885607 _Toc320885607 Anchor _Toc320885608 _Toc320885608 Anchor _Toc320885609 _Toc320885609 Anchor _Toc320885610 _Toc320885610 Anchor _Toc320885611 _Toc320885611 Anchor _Toc320885612 _Toc320885612 Anchor _Toc320885613 _Toc320885613 Anchor _Toc320885614 _Toc320885614 Anchor _Toc320885615 _Toc320885615 Anchor _Toc320885616 _Toc320885616 Anchor _Toc320885617 _Toc320885617 Anchor _Toc320885618 _Toc320885618 Anchor _Toc320885619 _Toc320885619 Anchor _Toc320885620 _Toc320885620 Anchor _Toc320885522 _Toc320885522
Only electrical utilization equipment that has been approved by the AHJ may be used at Berkeley Lab. Electrical utilization equipment that has been Accepted, Certified, Labeled, or Listed by an NRTL is considered acceptable to the AHJ, and is approved for use provided the equipment is installed and used within the manufacturer's listing intent. Electrical utilization equipment that has NOT been Accepted, Certified, Labeled, or Listed by an NRTL is not acceptable to the AHJ unless it has satisfactorily passed a documented safety inspection. To meet this requirement, Berkeley Lab has established the EESP.Anchor _Toc320885621 _Toc320885621
Upon installation, and prior to energization, newly purchased or Berkeley Lab–built electrical utilization equipment:
- Must receive an initial survey (Work Process C, Equipment Surveys)
- That is not NRTL Listed must be inspected by an Electrical Equipment Inspector and approved by the AHJ (Work Process D, Inspecting and Approving Electrical Equipment)
...